Microprocessor based Fire Alarm Control Panel
|
|
|
|
|
*
|
No. Of Zones : 4 to 64 Zones
|
|
*
|
Primary Power : 230 V AC, 50 Hz
|
|
*
|
Standby Power : 24v DC
|
|
|
( 2 Nos. of 12v, 7Ah S.M.F. Battery)
|
|
*
|
Zone Input : 2 Wire loop with 4K7 End Of Line Reg.
(EOL)
|
|
|
|
|
*
|
Standard Indication : System On / AC on / Battery On /
|
|
|
Low Battery / Charger On/ Walk Test /
|
|
|
Auxiliary Trip / Earth Fault
|
|
*
|
Operating Voltage : 24v DC
|
|
*
|
Normal Loop Voltage : 20.4v DC [Approximately]
|
|
*
|
Operating Current : 80mA plus 4.2mA per Zone
|
|
*
|
Open Threshold Current : 4.2mA
|
|
*
|
Short Circuit Threshold Current : 40mA
|
|
*
|
Standby Threshold Current : 8.2mA
|
|
*
|
(EOL Current + Detectors' Current)
|
|
*
|
Alarm Current : 20 - 35mA
|
|
*
|
Operating Conditions : -10 to 45 C, 30 - 95 % RH
|